Поиск
Eng

Capacitors of type SM and SMA

Capacitors of type SM and SMA

In the process of network development of high-voltage electricity transmission lines, an increase of their extension and equipping with automatic devices, it arises the need in reliable dispatching, administrative and economic communication between separate points, transmission of telemetry signals, emergency cutting off of switches, relay protection and other data. Usually that kind of communication is transmitted directly along high-voltage electricity transmission lines at a frequency of 40-500 kHz. One of the elements of equipment of such communication is coupling capacitors that separate coupling devices from high voltage of frequency 50 Hz passing signals of high frequency along communication channels. On the basis of same capacitors the devices are made for taking off the power at a frequency of 50 Hz directly from electricity transmission lines for supply of measuring instruments and power equipment as well as measuring devices (dividers, voltage transformers) for voltage measuring of electricity transmission lines.
Capacitors are made with an application of film dielectric. In agreement with the customer it is possible to manufacture capacitors for voltage 110/√3 kV with a paper-film dielectric. In this case, the letters “BP” are in the designation of capacitor type.
     Coupling capacitors are impregnated with ecologically safe fluid which is not in a prohibited list of Stockholm Convention about persistent organic pollutants (2001 year).

Application:
* for securing of high-frequency communication at frequencies from 24 up to 1500 kHz in electricity transmission lines with AC rated voltage 35, 110, 150, 220, 330, 500 kV frequency 50 and 60 Hz.
Capacitors are produced in porcelain insulators and impregnated with ecologically safe fluid.
**for connection of communication devices to electricity transmission lines from 6 up to 35 kV and lightning protection cables.
***for high-frequency trap installation;
**** capacitor of suspended performance for an active electrical power take-off from 50 Hz alternating current networks with a voltage 110 kV.

Type designation Tangent of loss angle Overall dimensions, mm Weight, kg Normative document
diameter height
 SM-66/√3-4,4 U1; HL1* 3,0×10-3 280 890 68±7 GOST 15581-80
 SMB-66/√3-4,4 U1*
 SMV-66/√3-4,4 U1; HL1* 935
 SMBV-66/√3-4,4 U1*
 SMP-66/√3-4,4 U1* 1300 106±12
 SMPB-66/√3-4,4 U1*
 SMPV-66/√3-4,4 U1* 1345
 SMPBV-66/√3-4,4 U1*
 SM-110/√3-6,4 U1* 330 1170 140±14
 SM-110/√3-6,4 HL1*1) 1380 180±18
 SMB-110/√3-6,4 U1*1)
 SMV-110/√3-6,4 U1* 1215 140±14
 SMV-110/√3-6,4 HL1*1) 1425 180±18
 SMBV-110/√3-6,4 U1*1)
 SMP-110/√3-6,4 U1* 1580 190±20
 SMPB-110/√3-6,4 U1*1) 1790 230±24
 SMPV-110/√3-6,4 U1* 1625 190±20
 SMPBV-110/√3-6,4 U1*1) 1835 230±24
 SM-66/√3-4,4 UHL1* 280  890 68±7 As per approved technical data sheet
 SMB-66/√3-4,4 HL1; UHL1*
 SMV-66/√3-4,4 UHL1* 935
 SMBV66/√3-4,4 HL1; UHL1*
 SMP-66/√3-4,4 HL1; UHL1* 1300 106±12
 SMPB-66/√3-4,4 HL1; UHL1*
 SMPV-66/√3-4,4 HL1; UHL1* 1345
 SMPBV-66/√3-4,4 HL1; UHL1*
 SM-110/√3-3,2 U1* 330 1170 140±14
 SM-110/√3-3,2 HL1; UHL1*1) 1380 180±18
 SMB-110/√3-3,2 U1; HL1; UHL1*1)
 SMV-110/√3-3,2 U1* 1215 140±14
 SMV-110/√3-3,2 HL1; UHL1*1) 1425 180±18
 SMBV110/√3-3,2 U1; HL1; UHL1*1)
 SMP-110/√3-3,2 U1* 1580 190±20
 SMP-110/√3-3,2 HL1; UHL1*1) 1790 230±24
 SMPB-110/√3-3,2 U1; HL1; UHL1*1)
 SMPV-110/√3-3,2 U1* 1625 190±20
 SMPV-110/√3-3,2 HL1; UHL1*1) 1835 230±24
 SMPBV-110/√3-3,2 U1; HL1; UHL1*1)
 SM-110/√3-6,4 UHL1*1)  1380 180±18
 SMB-110/√3-6,4 HL1; UHL1*1)
 SMV-110/√3-6,4 UHL1*1) 1425
 SMBV110/√3-6,4 HL1; UHL1*1)
 SMP-110/√3-6,4 HL1; UHL1*1) 1790 230±24
 SMPB-110/√3-6,4 HL1; UHL1*1)
 SMPV-110/√3-6,4 HL1; UHL1*1) 1835
 SMPBV-110/√3-6,4 HL1; UHL1*1)
 SM-110/√3-6,4 U1* 280 1170 83±6
 SM-110/√3-6,4 HL1; UHL1*1) 1380 100±6
 SMB-110/√3-6,4 U1; HL1; UHL1*1)
 SMV-110/√3-6,4 U1* 1215 83±6
 SMV-110/√3-6,4 HL1; UHL1*1) 1425 100±6
 SMBV110/√3-6,4 U1; HL1; UHL1*1)
 SMP-110/√3-6,4 U1* 1580 131±14
 SMP-110/√3-6,4 HL1; UHL1*1) 1790 148±14
 SMPB-110/√3-6,4 U1; HL1; UHL1*1)
 SMPV-110/√3-6,4 U1* 1625 131±14
 SMPV-110/√3-6,4 HL1; UHL1*1) 1835 148±14
 SMPBV-110/√3-6,4 U1; HL1; UHL1*1)
 SM-BP-110/√3-6,4 U1* 330 1170 140±14
 SM-BP-110/√3-6,4 HL1; UHL1*1) 1380   180±18
 SMB-BP-110/√3-6,4 U1; HL1; UHL1*1)
 SMV-BP-110/√3-6,4 U1* 1215 140±14
 SMV-BP-110/√3-6,4 HL1; UHL1*1)   1425 180±18
 SMBV-BP-110/√3-6,4 U1; HL1; UHL1*1)
 SMP-BP-110/√3-6,4 U1* 1580 190±20
 SMP-BP-110/√3-6,4 HL1; UHL1*1) 1790 230±24
 SMPB-BP-110/√3-6,4 U1; HL1; UHL1*1)
 SMPV-BP-110/√3-6,4 U1* 1625 190±20
 SMPV-BP-110/√3-6,4 HL1; UHL1*1) 1835 230±24
 SMPBV-BP-110/√3-6,4 U1; HL1; UHL1*1)
 SM-BP-110/√3-6,4 U1* 280 1170 83±6
 SM-BP-110/√3-6,4 HL1; UHL1*1) 1380 100±6
 SMB-BP-110/√3-6,4 U1; HL1; UHL1*1)
 SMV-BP-110/√3-6,4 U1* 1215 83±6
 SMV-BP-110/√3-6,4 HL1; UHL1*1) 1425 100±6
 SMBV-BP-110/√3-6,4 U1; HL1; UHL1*1)
 SMP-BP-110/√3-6,4 U1* 1580 131±14
 SMP-BP-110/√3-6,4 HL1; UHL1*1) 1790 148±14
 SMPB-BP-110/√3-6,4 U1; HL1; UHL1*1)
 SMPV-BP-110/√3-6,4 U1* 1625 131±14
 SMPV-BP-110/√3-6,4 HL1; UHL1*1) 1835 148±14
 SMPBV-BP-110/√3-6,4 U1; HL1; UHL1*1)
 SMM-20/√3-35 U1** 2,3×10-3 305×135×345 8±0,8 СТ 2347-1917-01-ТОО-4-064-2017
 SMM-20/√3-74 U1** 305×135×440 14±1,4
 SMM-20/√3-107 U1**

In capacitors designation first number after type – rated voltage in kV;
second – capacitance in nanofarad;
C – coupling capacitor;
M – impregnation with oil;
B – category of electrical equipment as per external insulation;
V – with terminal;
P – combined with insulating support;
M – capacitors are made in metal cases;
BP – paper-film dielectric.

Type designation Tangent of loss angle Overall dimensions, mm Weight, kg Normative document
diameter1) height
 SMA-110/√3-6,4 UHL1*2) 2,5×10-3 313 1272 130±10 СТ 2347-1917-01-ТОО-4-065-2017
 SMAV-110/√3-6,4 UHL1*2) 1305
 SMAP-110/√3-6,4 UHL1*2) 1705 172±10
 SMAPV-110/√3-6,4 UHL1*2) 1738
 SMA-133/√3-18,6 UHL1*2) 485 1454 300±30
 SMAV-133/√3-18,6 UHL1*2) 1486
 SMA-166/√3-14 UHL1*2) 1454
 SMAB-166/√3-14 UHL1*2)
 SMAV-166/√3-14 UHL1*2) 1486
 SMABV-166/√3-14 UHL1*2)
 SMA-166/√3-18 UHL1*2) 1454
 SMAB-166/√3-18 UHL1*2)
 SMAV-166/√3-18 UHL1*2) 1486
 SMABV-166/√3-18 UHL1*2)
 SMA-188/√3-12 UHL1*2) 1454 As per approved technical data sheet
 SMAV-188/√3-12 UHL1*2) 1486
 SMA-220/√3-3,2 UHL1* 313 2064 230±20
 SMAV-220/√3-3,2 UHL1* 2099
 SMA-110/√3-6,4 UHL1*2) 284 1272 130±10
 SMAV-110/√3-6,4 UHL1*2) 1305
 SMAP-110/√3-6,4 UHL1*2) 1705 172±10
 SMAPV-110/√3-6,4 UHL1*2) 1738
 SMA-133/√3-18,6 UHL1*2) 460 1454 300±30
 SMAV-133/√3-18,6 UHL1*2) 1486
 SMA-166/√3-14 UHL1*2) 1454
 SMAB-166/√3-14 UHL1*2)
 SMAV-166/√3-14 UHL1*2) 1486
 SMABV-166/√3-14 UHL1*2)
 SMA-166/√3-18 UHL1*2) 1454
 SMAB-166/√3-18 UHL1*2)
 SMAV-166/√3-18 UHL1*2) 1486
 SMABV-166/√3-18 UHL1*2)
 SMA-188/√3-12 UHL1*2) 1454
 SMAV-188/√3-12 UHL1*2) 1486
 SMA-К-110/√3-6,4 UHL1* 284 1272 70±10
 SMAV-К-110/√3-6,4 UHL1* 1305
 SMAP-К-110/√3-6,4 UHL1* 1705 110±10
 SMAPV-К-110/√3-6,4 UHL1* 1738
 SMA-К-133/√3-18,6 UHL1* 400 1454 166±30
 SMAV-К-133/√3-18,6 UHL1* 1486
 SMA-К-166/√3-14 UHL1* 1454
 SMAV-К-166/√3-14 UHL1* 1486
 SMA-К-166/√3-18 UHL1* 1454
 SMAV-К-166/√3-18 UHL1* 1486
 SMA-К-188/√3-12 UHL1* 1454
 SMAV-К-188/√3-12 UHL1* 1486
 SMA-BP-110/√3-6,4 UHL1*2) 313 1272 130±10
 SMAV-BP-110/√3-6,4 UHL1*2) 1305
 SMAP-BP-110/√3-6,4 UHL1*2) 1705 172±10
 SMAPV-BP-110/√3-6,4 UHL1*2) 1738
 SMA-BP-110/√3-6,4 UHL1*2) 284 1272 130±10
 SMAV-BP-110/√3-6,4 UHL1*2) 1305
 SMAP-BP-110/√3-6,4 UHL1*2) 1705 172±10
 SMAPV-BP-110/√3-6,4 UHL1*2) 1738
 SMA-BP-К-110/√3-6,4 UHL1* 1272 70±10
 SMAV-BP-К-110/√3-6,4 UHL1* 1305
 SMAP-BP-К-110/√3-6,4 UHL1* 1705 110±10
 SMAPV-BP-К-110/√3-6,4 UHL1* 1738
 SMAV-110/√3-6,4 UHL1*** 230 1422 55±5
 SMAV-BP-110/√3-6,4 UHL1***

In capacitors designation first number after type – rated voltage in kV;
second – capacitance in nanofarad;
C – coupling capacitor;
M – impregnation with oil;
A – in reinforced insulator;
B – category of electrical equipment as per external insulation;
V – with terminal;
P – combined with insulating support;
BP – paper-film dielectric.
K – capacitors are made in a composite case with silicone ribbing.

1) – Depending on the insulators performance there may be differences in the overall and mounting dimensions of capacitors (indicated in brackets). The required dimensions are specified at ordering.
2) – In agreement with the customer, it is possible to manufacture capacitors with a creepage distance of external insulation corresponding to the III or IV degree of pollution according to GOST 9920-89.